10 COOL or HEAT Mode 1. In either mode, press the button to increase or button to decrease the temperature set point of the active mode. The dis
11 6. Press Hum again and the display will show the “d” (differential) “d” means the differential: the setting starts from 2.0 to a maximum of 4 in i
12Your specific unit alarm functions can be determined by looking at the unit wiring diagram. Alarms 1 and 2 are critical alarms. When activated t
13 B. Setting the time of program for weekdays schedule 1. Press the Prog button. Program 1 and the weekdays will appear on the display. 2. Pr
14NOTE: The controller keeps a differential of at least 1 degree between the HEAT set point and COOL set point (HEAT is always less than COOL).
15 Table 1a Weekly Schedule Program No. Time Temp Hour Minutes Heat Cool Humidity 1 2 3 4 Table 1b Saturday Sch
16f. Plug the cable back into the board and re-attach the DISPLAY with the bottom piece. g. The controller will have to be fully re-programmed.
17 UNITED COOLAIR CORPORATION 491 East Princess Street York, PA 17403 (717) 843-4311 (877) 905-1111 Fax (717) 854-4462 ww
2MP CONTROLLER INSTALLATION & OPERATING MANUAL UNITED COOLAIR CORPORATION 491 E. Princess Street York. PA 17403 (717)
3TABLE OF CONTENTS GENERAL INFORMATION 3 MP CONTROLLER COMPONENTS 3 Main Board 3 Temperature / Humidity Sensor
4 GENERAL INFORMATION Read and save this installation and operating manual before proceeding with installing or operating the MP CONTROLLER. 1. The M
5 Display The display (Fig 3) provides information on the state of the controller. It also serves as the interface for controlling the operating para
6 1. ON/OFF button: Press to turn the unit on. Press and hold for about 3 seconds to turn the unit off. 2. button: Press this button to increas
7INSTALLATION OF THE COMPONENTS NOTE: The Main Board (Fig 1) is factory installed and is located inside the unit. The procedure for field installati
8Installation materials and tools 4-conductor 18-guage shielded wire (field supplied) Small straight screwdriver. Power drill and drill bits
9 Step 5. Attach the bottom piece to the wall using the two screws. CAUTION: Make sure sensor is positioned in the proper orientation per the label o